Faults and Protection

Faults

causes leading to disturbances
   unintended circuit interruption, broken conductor
   overload: load currents exceed rated values of the equipment (lines, transformers)
      overload tripping of line may result in overloads of other lines (cascading overload tripping)
   unintended connection between conductors of different phases => short circuit
   unintended connection between phase and ground => earth fault
      low impedance grounding of the transformer neutral
         => short circuit, must be switched off by the protection immediately
      isolated transformer neutral => earth fault, disconnection not necessary
      earth fault compensation, reactance between transformer neutral and earth reduces earth fault current
         not necessary to switch off earth fault, continuous service with earth fault
            phase to ground voltages during earth fault: faulted phase 0 V, healthy phases nominal x sqrt(3)
         system with earth fault can be operated for one or two hours,
            but risk of double earth fault because of increased voltage in healthy phases


fault types
   three phase short circuit, symmetrical
   two phase, phase to phase short circuit
   two phase short circuit with ground
   earth fault

   during fault: abnormal current and voltage conditions
   permanent faults
   temporary faults
      arc extinguishes, faults removed by deenergizing the faulted equipment


connection of transformer neutral
   transformer neutral
      low impedance grounding
      isolated transformer neutral
      peterson coil, earth fault compensation
   low impedance grounding (EHV, HV, (MV)
      earth fault => short circuit, must be switched off immediately
      disadvantage: high fault currents, service interruption
      advantage: defined fault location, faulted line is tripped

   isolated transformer neutral (special cases: industrial plants, mines)
      earth fault => no short circuit, earth fault current only because of line capacitance, continued operation
         earth fault must be found and can be switched off without consumer interruption
         phase to ground voltage of healthy phases => phase to phase voltage
      advantage: no interruption of service for single earth fault, low fault currents
      disadvantage: high voltage (sqrt(3) x UN) in healthy phases of all lines, difficult to find
   earth fault compensation HV, MV
      earth fault current further reduced by reactance between transformer neutral and ground

Protection

objectives of protection schemes
   prevent damage of equipment
      clear short circuits as quick as possible
      extinguish arc
   prevent expansion of a disturbance


   maintain continuous supply to customers
      limit fault to an area as small as possible
      smallest possible area to be disconnected
      restore supply quickly


principles of protection schemes
   selectivity
      switch off the minimum possible part of the network
   clear fault as quick as possible
      < 100 ms (first time zone of distance protection) up to a few seconds (overcurrent relay)
      burning arc causes damage
   protection range
      time step shall cover max. area
   reliability
      backup protection
         time zones

protection devices (relays)

Overcurrent Protection

Protection_vsd~Overcurrent.png Protection_vsd~Directional.png
   overcurrent protection   > I
      used in medium and low voltage networks
      protection against short circuits and overloads
      overcurrent relays (medium and low voltage)
         current measurement
         circuit breaker receives tripping signal from over current relay
      fuses (medium and low voltage)
         conductor melts, if current is above rated current
         cheap
         reclosure: replace fuse (no remote control)
         additional load disconnector required
      selectivity by increasing delay
         => disadvantage: longest delay for faults near injection where the short circuit current is highest


Distance Protection

Protection_vsd~Measurements.png Protection_vsd~Impedance.png Protection_vsd~Distance.png Protection_vsd~Coordination.png
   distance protection   < Z
      extra high voltage (EHV), high voltage (HV), medium voltage (MV)
         current and voltage measured
      impedance is determined form voltage and current
      loop impedance is proportional to distance between the relay and the short circuit
      circuit breaker receives tripping signal from distance relay
      time steps
         quick tripping, if impedance is in the lowest impedance zone
         delayed tripping, if impedance is in higher impedance zone
            => backup protection, if relay closer to the fault fails


*** your browser settings do not support java *** dynamic applet replaced by static image *** distance_protection_demo.png *** your browser settings do not support java *** dynamic applet replaced by static image ***
Protection_vsd~Differential.png
   differential protection
      used for bus bars, transformers, generators, (short lines)
      total of incoming and outgoing currents must equal zero, deviation in case of a fault

      transformers: currents different on primary and secondary side of the transformer
         unified secondary current (1 or 5A) of current-transformer (instrument transformer)

Protection_vsd~TrafoDiff.png Protection_vsd~Reclosure.png
   automatic reclosure  (for overhead lines)
      sequence of events
         relay recognizes fault
         circuit breaker trips after < 100 ms
         automatic reclosure after 500...700 ms
         if arc is extinguished in the meantime => successful reclosure
         otherwise permanent fault => final tripping of the line after ~100 ms

n-1-security

(see slides in 2_Switching\Netzbetrieb_englisch.ppt)

n-1-criterion
   system shall withstand single outage without expansion of the disturbance


HV, EHV
   no influence on consumers for single fault
   meshed network operations
   redundancy
   checked by loadflow calculations
      outage simulation, contingency analysis
         simulate each single outage, check for overloads and limit violations after line outages
         avoid cascading: (overload) tripping of a line results in overloads of other lines

MV
   open loops, not meshed
   consumers interrupted for a limited time (30 min ... 2 h)
      interruption tolerated for a limited period of time
      possibility to restore supply by (manual) switching
      if available, close sectioning switch
      otherwise, bring mobile generator to the consumer site